4Ć104 FST Configuration
Original Ć June 1990CE4.2:CL6211
IFTOSP IFTOSP
50
INSTRUCTION NAME: IFTOSP (if true, operator station primary point)
DESCRIPTION: This instruction switches the operator station specified by operand 2 to the
primary DCP based on the logical state of the logic value specified by operand 1. This function is
used with double or cascade operator station types. The SVA and SVD inputs remain unchanged.
CONFIGURATION FORMAT: IFTOSP (
Logic signal >>
Operator station port # >>
Comment >>
OPERAND DESCRIPTIONS:
Logic signal - The name of the general register or discrete loadable function that contains the
logic value.
Operator station port # - The number assigned to the operator station. See Operator Station
definition section, Table 4Ć2 on page 4Ć9 for possible operator station port numbers for each
controller type.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
If logic value = 0
Then selected DCP is unchanged
If logic value = 1
Then Primary DCP is selected
SVA(out) = SVA(in)
SVD(out) = SVD(in)