INSTRUCTION NAME: FDFWM (feedforward multiply only)
DESCRIPTION:
This instruction multiplies the SVA input by a feedforward scale factor. When the
multiplier function (operand 1) is enabled, operands 2, 3, and 4 combine to generate the
feedforward output. When operand 3 is set to reverse, the multiplier value (operand 4) will be
subtracted from 1.0, scaled by the multiplier gain (operand 2), and multiplied by the SVA input to
produce the SVA output. When multiplier REV/DIR (operand 3) is set for direct actions, the SVA
input, the multiplier value (operand 4) and the multiplier gain (operand 2) are multiplied together to
produce the SVA output. The SVD input remains unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
T
T
n
1.0
X
k
OPERAND 4
OPERAND 3
OPERAND 2
OPERAND 1
CONFIGURATION FORMAT: FDFW (
Multiplier enable >>
Multiplier gain >>
Multiplier REV/DIR >>
Multiplier value >>
Comment >>