4Ć112 FST Configuration
Original Ć June 1990CE4.2:CL6211
LIMIT LIMIT
57
INSTRUCTION NAME: LIMIT (limiter)
DESCRIPTION : This instruction places upper and lower limits on the SVA input. The SVA input is
compared to the high limit contained in operand 1 and the low limit contained in operand 2. When
the SVA input is between (or equal to) these limit values, the SVA output equals the SVA input and
the SVD output equals 0.
When the SVA input is lower than the low limit value, the SVA output equals the low limit value, and
the SVD output equals 1. When the SVA input is higher than the high limit value, the SVA output
equals the high limit value and the SVD output equals 1.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
0
t
0
t
1
INPUT
OUTPUT
1
t
2
0
1
SVD
OPERAND 1 -
t
3
HIGH
LIMIT
OP 1
OP 2
LOW
LIMIT
t
0
t
1
t
2
t
3
SVD
LOW LIMIT
OPERAND 2 -
HIGH LIMIT
23
CONFIGURATION FORMAT: LIMIT (
Upper Limit Value >>
Lower Limit Value >>
Comment >>
OPERAND DESCRIPTIONS:
Upper limit value - The name of the general register or analog loadable function that contains the
high limit.
Lower limit value - The name of the general register or analog loadable function that contains the
low limit.
Comment - A comment up to 255 characters long.
(Continued on next page)