4Ć36 FST Configuration
Original Ć June 1990CE4.2:CL6211
AINEU AINEU
5
INSTRUCTION NAME: AINEU (analog input in engineering units)
DESCRIPTION: This instruction sets the SVA output equal to the value, in engineering units, of
the analog input at the channel specified by operand 1. The engineering units used to convert the
input are specified by values in operand 2. The SVD output is 0 if the analog input value is between
-2 and 102 percent of span. If the analog input value is outside of this range, the SVD output is 1.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
20 mA
4 mA
t
0
t
1
INPUT
EUHV
EULV
t
0
t
1
OUTPUT
( ) T
%
!
EU
CONFIGURATION FORMAT: AINEU (
AIN channel >>
Eng conversion factors >>
Comment >>
OPERAND DESCRIPTIONS:
AIN channel - The channel number of the desired analog input. The relationship between AIN
channel number for each analog input function and the actual field wiring terminal designations is
as follows:
Field wiring
Controller type Terminal designation AIN channel number
Computing MV1+ to MV5+ 1 to 5
2-Wide MV1+ to MV10+ 1 to 10
3-Wide Discrete MV1+ to MV10+ 1 to 10
3-Wide Analog MV1+ to MV10+ 1 to 10
MV16+ to MV20+ 16 to 20
4-Wide MV1+ to MV20+ 1 to 20
(Continued on next page)