4Ć93FST Configuration
Original Ć June 1990 CE4.2:CL6211
ICPLDA ICPLDA
41
INSTRUCTION NAME: ICPLDA (indirect control point load analog)
DESCRIPTION: This instruction sets the SVA output equal to the analog indirect control point
(ICP) value contained in operand 2. Operand 1 contains the ICP name. The ICP value contained in
operand 2 is in units of percent. Before becoming the SVA output, the ICP value is converted to
engineering units (E.U.'s) using the engineering units high value (EUHV) and the engineering units
low value (EULV) of the ICP contained in operand 1. The SVD input remains unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
ICP
REG 1 REG 2
OPERAND 2
T
% !
EU
CONFIGURATION FORMAT: ICPLDA (
ICP tag >>
ICP reg number >>
Comment >>
(Continued on next page)