4-25Input and Output Cards
Original — December 1991 UM4.6:CS6003
Step 5: Press the calibrator MUX switch. The calibrator numerical
display shows one of the following:
No Code — The card requires repair; terminate procedure
and obtain a replacement card
0003 — The card is a pulse count input card; continue
procedure
Any Other Code — The card is not a pulse count input
card or requires repair; terminate procedure and obtain a
replacement card
Step 6: Press the calibrator A12 group mode switch.
Step 7: Set the calibrator CHANNEL SELECT switch to channel 1.
Step 8: Verify that the pulse or waveform signal generator is off.
Connect the pulse or waveform generator between the
calibrator breakout terminals for channel 1 (see Table 4-12).
Table 4-12. Calibrator Breakout Terminal Assignments for
Pulse Count Input Cards
Breakout Terminal Function
1 Channel 1 +
2 Channel 1 –
3 Channel 2 +
4 Channel 2 –
5 Channel 3 +
6 Channel 3 –
7 Channel 4 +
8 Channel 4 –
9 No connection
10 No connection
11 No connection
12 No connection
13 No connection
14 No connection
15 No connection
16 No connection
17 +24 volts
18 +24 volts
19 24 volt return
20 24 volt return